VYF Centrifugal Roof Extract Fans

VYF Horizontal Roof Extract Fans:

• Working temperature: +120 ºC.

• High corrosion-resistant aluminum roof cowl

• High efficient backward curved impeller is made up of galvanized steel sheet

• The bird protection guard and roof base support are made up of galvanized steel sheet

Motor :

• The fans are composed of backward sloping and infrequently arranged fins.
• Single-Three phase 220-240-380V 50Hz.

• Class F motors.

• Standard asynchronous motors with IP 55 and F class insulation

• Frequency inverters are optional to control the capacity in the range of %25 – %100.

• The motor is outside of the air stream

Description

VYF Centrifugal Roof Extract Fans from Breezsol

VYF Centrifugal Roof Extract Fans from Breezsol in Dubai, UAE, and Gulf Countries are widely used in industry & agriculture.

 

Roof Extract Fans pull air out of a building and force it into the room by using their highly efficient powerful motor. This causes a positive pressure differential in the room forcing air out, while at the same time producing a negative pressure differential inside the living areas.

Normally, with Roof Extract Fans, the air change efficiency can reach up to 90%-97%. So they are widely used in industry & agriculture, such as heat treatment plants, casting plants, plastics plants, aluminum plants, electroplating plants, chemical plants, greenhouses, livestock farms, garment factories, etc. We also deal in Straight and Natural Roof Ventilators. Check our Facebook page for ongoing offers and promotions.

 

Application

  1. Industrial fields: textile, socks/clothes making, glass, coating, silk-screen printing, printing, foodstuff, processing, dyeing, laundry with high temperature.
  2. Civil fields: net bars, stores, supermarkets, mess hall, food markets, waiting-rooms and recreation places and other occasions with air-conditioning.
  3. Agricultural & horticulture fields: large farms, greenhouse and livestock farms, etc.

 

This group includes Horizontal Roof Extract Fans, Centrifugal Roof Extract Fans, Vertical Discharge Centrifugal fans, and Roof Axial Extract Fan. The two different horizontal and vertical blow types are manufactured from roof fans.

Model Voltage

(V)

Frequency

(Hz)

Power

KW

Current

A

Speed

r.p.m

Airflow

(m3/h)

Sound Pressure

Db(A)

Weight

(kg)

VYF 280 230 / 380 50 0,25 1,82 / 0,79 1400 1100 46 35
VYF 315 230 / 380 50 0,37 2,54 / 1,15 1400 2200 43 42
VYF 355 230 / 380 50 0,55 3,38 / 1,60 1400 3400 44 50
VYF 400 230 / 380 ­50 0,75 4,60 / 2,10 1400 4300 49 55
VYF 450 230 / 380 50 1,10 7,30 / 2,60 1400 5800 52 62
VYF 500 230 / 380 50 1,50 9,20 / 3,50 1400 8500 54 68
VYF 560 230 / 380 50 2,2 13,60 / 5,00 1400 10500 56 75
VYF 630 230 / 380 50 3 19,00 / 6,60 1400 12800 50 127
VYF 710 380 50 4 – / 8,20 1400 15000 53 150
VYF 800 380 50 5,5 – / 11,20 1400 17500 56 216