VLF-BS Box Type Smoke Extract Fans

VLF-BS Box Type Smoke Extract Fans:

• Fan box made in steel sheet and hot-dip galvanized-corrosion resistant.

• Approved by standard EN 12101-3, with certification APPLUS (F400°C) and (F300°C).

• 400 – 1250 mm diameter

• Adjustable pitch impellers.

• Volumes up to 155,500 m³/h (43.2 m³/s)
• 100% reversible impellers.

Motor:

• Motors with IE2 and IE3 efficiency. 2,4 and 6 pole motor options.
• Class H motors with ball bearings and IP55 protection.
• Three-phase 380-400V 50Hz.
• Fans with 2-speed motor.

• Speed controllable by voltage reduction.

• 2 hours of continuous operation at 400°C and 300°C

Description

VLF-BS Box Type Smoke Extract Fans from Breezsol

VLF-BS Box Type Smoke Extract Fans from Breezsol in Dubai, UAE, and Gulf Countries are widely used in industry & agriculture.

 

Smoke Extract Fans pull out hot air, smoke, and gasses from the building and force them into the room during a fire by using their highly efficient powerful motor. This causes a positive pressure differential in the building forcing hot air out, smoke, and gasses while at the same time producing a negative pressure differential inside the living areas.

The most common smoke extract fans are open just like a window or skylight that offer an escape route for smoke and hot air. So they are widely used in industry & agriculture, such as heat treatment plants, casting plants, plastics plants, aluminum plants, electroplating plants, chemical plants, greenhouses, livestock farms, garment factories, etc. We also deal in Horizontal and Extract Roof Ventilators. Check our Facebook page for ongoing offers and promotions.

 

Application

  1. Industrial fields: textile, socks/clothes making, glass, coating, silk-screen printing, printing, foodstuff, processing, dyeing, laundry with high temperature.
  2. Civil fields: net bars, stores, supermarkets, mess hall, food markets, waiting-rooms and recreation places and other occasions with air-conditioning.
  3. Agricultural & horticulture fields: large farms, greenhouse and livestock farms, etc.

 

This group includes Horizontal Roof Extract Fans, Centrifugal Roof Extract Fans, Vertical Discharge Centrifugal fans, and Roof Axial Extract Fan. Smoke Extract fans are manufactured in two different types horizontal and vertical blow.

This group includes Smoke Extract Car Park Fans, Smoke Extract Tubular Axial Fan. Every situation should be taken into consideration in case of fire. Therefore, the necessary smoke evacuation system and extinguishing systems must be installed correctly to prevent the growth and expansion of the flames. Smoke evacuation fans are of great importance for the life of the living creatures in the environment. It eliminates risks such as smoke poisoning. For this reason, a powerful fan should be preferred.

Model Voltage (V) Frequency (Hz) Power (KW) Speed (r.p.m) Airflow (m³/h) Sound Pressure dB(A)
VLF-BS / 400 / 6 / 2P 230-400 50 2,2 2880 9540 70
VLF-BS / 400 / 6 / 4P 230-400 50 0,75 1410 5100 54
VLF-BS / 450 / 6 / 2P 230-400 50 3,00 2880 12750 73
VLF-BS / 450 / 6 / 4P 230-400 50 0,75 1410 7300 58
VLF-BS / 500 / 6 / 2P 230-400 50 5,50 2880 18450 75
VLF-BS / 500 / 6 / 4P 230-400 50 1,10 1410 12000 62
VLF-BS / 560 / 6 / 2P 230-400 50 7,50 2910 27100 81
VLF-BS / 560 / 6 / 4P 230-400 50 2,20 1440 16000 64
VLF-BS / 630 / 6 / 2P 230-400 50 11,00 2930 30000 87
VLF-BS / 630 / 6 / 4P 230-400 50 3,00 1440 21350 69
VLF-BS / 710 / 6 / 4P 230-400 50 4,00 1440 28750 73
VLF-BS / 800 / 6 / 4P 230-400 50 7,50 1440 39000 77
VLF-BS / 800 / 9 / 4P 230-400 50 7,50 1440 40400 77
VLF-BS / 900 / 6 / 4P 230-400 50 15,00 1440 57200 81
VLF-BS / 900 / 9 / 4P 230-400 50 18,50 1440 59000 82
VLF-BS / 1000 / 6 / 4P 230-400 50 22,00 1440 79000 84
VLF-BS / 1000 / 9 / 4P 230-400 50 30,00 1440 81000 85
VLF-BS / 1250 / 6 / 4P 230-400 50 55,00 1440 145000 92
VLF-BS / 1250 / 9 / 4P 230-400 50 45,00 1440 131400 88